Fault Analysis and Handling of Otis MCS220 GEN-II Elevator Weighing Device

Time:2024-06-12   Source:江西天虹机电有限公司   Views:2226

The earliest Otis GEN-II MCS220 elevator weighing system installed four weighing sensors and an LWB weighing board on the frame of the car floor. The weighing board was connected to the MCB-II board through CAN-BUS communication, and the four weighing sensors were used to obtain the weight analog voltage of passengers in the car. This allowed the GENG-II elevator to be given a reasonable pre torque when starting or stopping, providing good comfort when braking. When the comfort was abnormal, the service tool MCB-II board was tested, and the service tool error note M-2-2-1 was recorded. After pressing the shift+3 on the service tool, the following faults may occur


1. ALW: LWB Board


Possible reasons: internal errors or abnormalities in the weighing device board,


Solution: Replace the weighing device version LWB


2. ALW: Load Sensor


Possible causes of malfunction:


1) Detected at least one load cell malfunction or damage


Solution: Replace the weighing sensor


2) The GAIN data of the weighing device board is abnormal.


Solution: Perform GAIN correction adjustment


3) The output voltage of the sensor is abnormal, and the voltage is not between 2000 (2V-7V) millivolts and 7000 millivolts


Solution: Adjust the pressure of the weighing sensor to a suitable range of 2000 (2V-7V) millivolts to 7000 millivolts


3. ALW: CAN Bus


1) Fault cause, possible cause: communication loss between MCB-II board and LWB2 board


Solution: Check the connection of the CAN communication line


2) Abnormal power supply on LWB2 board


Solution: Check MCB P5:6- MCB P5:5 DC (+15V) (HL2)


3) MCB-II board damaged


Solution: Replace the MCB-II board.




Copyright © Jiangxi Tianhong Electromechanical Co., Ltd. Contact person: 19917177918 Ms. Huang landline number: 0797-8220752

QQ:2993817878   Address: No. 19-4 Pingfengling Road, Economic and Technological Development Zone, Ganzhou City, Jiangxi Province Technical Support:江西华邦LOGO白色.png

备案号:赣ICP备18014169号-1

Mobile website

Official WeChat



Fault Analysis and Handling of Otis MCS220 GEN-II Elevator Weighing Device

2024-06-12

The earliest Otis GEN-II MCS220 elevator weighing system installed four weighing sensors and an LWB weighing board on the frame of the car floor. The weighing board was connected to the MCB-II board through CAN-BUS communication, and the four weighing sensors were used to obtain the weight analog voltage of passengers in the car. This allowed the GENG-II elevator to be given a reasonable pre torque when starting or stopping, providing good comfort when braking. When the comfort was abnormal, the service tool MCB-II board was tested, and the service tool error note M-2-2-1 was recorded. After pressing the shift+3 on the service tool, the following faults may occur


1. ALW: LWB Board


Possible reasons: internal errors or abnormalities in the weighing device board,


Solution: Replace the weighing device version LWB


2. ALW: Load Sensor


Possible causes of malfunction:


1) Detected at least one load cell malfunction or damage


Solution: Replace the weighing sensor


2) The GAIN data of the weighing device board is abnormal.


Solution: Perform GAIN correction adjustment


3) The output voltage of the sensor is abnormal, and the voltage is not between 2000 (2V-7V) millivolts and 7000 millivolts


Solution: Adjust the pressure of the weighing sensor to a suitable range of 2000 (2V-7V) millivolts to 7000 millivolts


3. ALW: CAN Bus


1) Fault cause, possible cause: communication loss between MCB-II board and LWB2 board


Solution: Check the connection of the CAN communication line


2) Abnormal power supply on LWB2 board


Solution: Check MCB P5:6- MCB P5:5 DC (+15V) (HL2)


3) MCB-II board damaged


Solution: Replace the MCB-II board.