The acceptance of elevator safety protection must comply with the following regulations:


1. Phase failure or misalignment protection device or function


When any one phase of the three-phase power supply in the control cabinet is disconnected or any two phases are wrongly connected, the protection device or function of the disconnected or wrongly connected phase should prevent dangerous faults from occurring in the elevator.


Note: When the phase mismatch does not affect the normal operation of the elevator, there may be no phase mismatch protection device or function.


2. Short circuit and overload protection devices


Power circuits, control circuits, and safety circuits must have short-circuit protection devices that match the load; The power circuit must have an overload protection device.


3. Speed limiter


The downward sign of the car (counterweight, counterweight) on the speed limiter must match the actual downward direction of the car (counterweight, counterweight). The rated speed and operating speed on the speed limiter nameplate must match the inspected elevator.


4. Safety gear


The safety gear must match its type test certificate.


5. Buffer


The buffer must match its type test certificate.


6. Door lock device


The door lock device must match its type test certificate.


7. Upper and lower limit switches


The upper and lower limit switches must be safety contacts and must operate normally during the action test at the end station position. Action must be taken before the elevator car or counterweight (if any) comes into contact with the buffer, and the buffer must remain in action when fully compressed.


8. The stop devices for the car roof, machine room (if any), pulley room (if any), and pit must operate normally.




Copyright © Jiangxi Tianhong Electromechanical Co., Ltd. Contact person: 19917177918 Ms. Huang landline number: 0797-8220752

QQ:2993817878   Address: No. 19-4 Pingfengling Road, Economic and Technological Development Zone, Ganzhou City, Jiangxi Province Technical Support:江西华邦LOGO白色.png

备案号:赣ICP备18014169号-1

Mobile website

Official WeChat



Regulations on Acceptance of Elevator Safety Protection

2024-06-12

The acceptance of elevator safety protection must comply with the following regulations:


1. Phase failure or misalignment protection device or function


When any one phase of the three-phase power supply in the control cabinet is disconnected or any two phases are wrongly connected, the protection device or function of the disconnected or wrongly connected phase should prevent dangerous faults from occurring in the elevator.


Note: When the phase mismatch does not affect the normal operation of the elevator, there may be no phase mismatch protection device or function.


2. Short circuit and overload protection devices


Power circuits, control circuits, and safety circuits must have short-circuit protection devices that match the load; The power circuit must have an overload protection device.


3. Speed limiter


The downward sign of the car (counterweight, counterweight) on the speed limiter must match the actual downward direction of the car (counterweight, counterweight). The rated speed and operating speed on the speed limiter nameplate must match the inspected elevator.


4. Safety gear


The safety gear must match its type test certificate.


5. Buffer


The buffer must match its type test certificate.


6. Door lock device


The door lock device must match its type test certificate.


7. Upper and lower limit switches


The upper and lower limit switches must be safety contacts and must operate normally during the action test at the end station position. Action must be taken before the elevator car or counterweight (if any) comes into contact with the buffer, and the buffer must remain in action when fully compressed.


8. The stop devices for the car roof, machine room (if any), pulley room (if any), and pit must operate normally.